MX 32 – Compact and flexible gas alarm center
The MX 32 from Teledyne Oldham Simtronics is a compact and user-friendly gas alarm center designed for continuous monitoring of flammable and toxic gases as well as oxygen. The center combines analog and digital communication in a flexible system with support for up to eight gas detectors.
With its compact design, programmable alarm functions and the ability to add external expansion modules, the MX 32 is an excellent option for smaller and medium-sized gas detection systems in industry, buildings and process plants.
Flexible and reliable gas monitoring
The MX 32 features a backlit 5-inch graphical LCD display that provides the operator with a clear overview of current gas concentrations, alarm levels, and system status. Up to eight gas detectors can be displayed simultaneously on the display.
The control panel supports both analog 4–20 mA signals and digital gas detectors. Through programmable relay outputs, the control panel can control external safety functions such as ventilation, magnetic valves, and sound and light alarms.
With the COM 32 configuration software, the alarm levels, relay functions, time delays, and alarm logic of the system can be adapted to meet the needs of the business.
Features and benefits
- Continuous monitoring of up to eight gas detectors.
- Support for analog and digital gas detectors.
- Compact and wall-mounted design.
- Backlit 5-inch graphic LCD display.
- Three programmable gas alarm levels per detector.
- Alarm for exceeding and under-measuring range.
- Four integrated programmable alarm relays.
- Separate relay for fire alarm.
- Possibility of external expansion modules.
- Modbus RTU communication as an option.
- Integrated alarm, fault and event log.
- Possibility of integrated audio and light alarm.
- Functional safety according to SIL 1.
- Enclosure class IP55.
Expansion possibilities
The MX 32 can be supplemented with external modules to expand the central’s functionality and adapt the system to the needs of the installation.
- Relay module with 4 or 8 programmable relay outputs.
- Input module with 8 analog inputs.
- Input module with 16 digital logic inputs.
- Output module with 4 analog 4–20 mA outputs.
The expansion modules can be placed close to detectors and external security functions, which simplifies installation and reduces the need for extensive cable routing.
Technical specifications
| Parameter | Technical specification |
|---|---|
| Manufacturers | Teledyne Oldham Simtronics |
| Model | MX 32 |
| Product type | Stationary gas alarm control panel |
| Number of gas detectors | Up to 8 |
| Analog inputs | 4–20 mA / Wheatstone bridge |
| Digital communication lines | Max. 2 |
| Display | 5-inch graphic LCD |
| Gas alarm levels | 3 per detector |
| Integrated Relays | 4 alarm relays + 1 error relay |
| External relays | Up to 16 |
| Relay capacity | 5 A / 250 VAC or 30 VDC |
| Analog outputs | Up to 8 × 4–20 mA |
| External communication | RS485 Modbus RTU (optional) |
| Supply voltage | 100–240 VAC or 22–28 VDC |
| Operating temperature | −20 to +50 °C |
| Humidity | 5–95 % RH |
| Protection class | IP55 |
| Dimensions (B × H × D) | 265 × 266 × 96 mm |
| Configuration software | COM 32 |
| Functional safety | SIL 1 according to EN 50271:2010 |
Event log and calibration
The MX 32 has an integrated event log with the capacity to store up to 512 alarm events, 512 error events, and 512 system events.
The central unit also features functions for presenting calibration curves and simplifying zero point and sensitivity adjustment, which facilitates service and maintenance.
Areas of application
- Industrial and process plants
- Heating plants and power stations
- Battery charging stations
- Refrigeration and freezing equipment
- Laboratories
- Water and treatment plants
- Garages and parking facilities
- Gas storage facilities and gas distribution centers
- Machine rooms and technical spaces