Choking gases are gases that can displace oxygen in the air. They are often colorless, odorless, and difficult to detect without measuring equipment. The risk is especially high in enclosed spaces such as tanks, shafts, silos, machine rooms, and processing plants.
| Gas | Chemical designation | Common areas of use | Risk |
|---|---|---|---|
| Nitrogen | N₂ | Food industry, process industry, laser cutting | Blocks oxygen from passing through and can cause a lack of oxygen. |
| Carbon dioxide | CO₂ | Breweries, food industry, refrigeration systems | High concentrations can cause asphyxiation. |
| Argon | Ar | Welding, metal industry, laboratories | It is heavier than air and can accumulate in low points. |
| Helium | He | Cooling technology, laboratories, leak detection | Displaces oxygen without being noticed. |
| Hydrogen* | H₂ | Battery room, energy storage, industry | Can cause oxygen deficiency at high concentrations. |
| Neon | No | Special lighting, laboratories | Inert gas that can reduce the oxygen content. |
| Krypton | Kr | Lighting, electronics industry | Can cause oxygen deficiency in enclosed environments. |
| Xenon | Xe | Medical technology, lighting, research | Inert gas that can displace oxygen. |
| Liquid nitrogen (vaporized) | N₂ | Cryogenic facilities, laboratories | Rapid evaporation can cause acute oxygen deficiency. |
| Liquid argon (vaporized) | Ar | Metal industry, process industry | Can quickly fill a space with an oxygen-poor atmosphere. |
*Hydrogen is usually monitored primarily due to the risk of fire and explosions, but it can also contribute to oxygen deficiency in enclosed spaces.
Therefore, asphyxiating gases are dangerous
Unlike toxic gases, asphyxiating gases do not directly affect the body. Instead, they reduce the oxygen content in the air. Because most of these gases are colorless and odorless, people often do not notice the danger until symptoms appear.
Normal and dangerous levels of oxygen
| Oxygen content | Effect |
|---|---|
| 20,9 % | Normal air |
| 19,5 % | Minimum recommended level for safe working environment |
| 16–19 % | Impaired concentration and performance ability |
| 10–16 % | Dizziness, rapid breathing and impaired judgment |
| 6–10 % | Risk of unconsciousness |
| Below 6% | Life-threatening, risk of death within minutes |
Common environments with a risk of oxygen deficiency
Tanks and reservoirs
Nitrogen is often used to inertize tanks to prevent fire and oxidation.
Breweries and the food industry
Carbon dioxide is used in production and can accumulate in low-lying areas.
Welding workshops
Argon and other protective gases can displace oxygen in the working environment.
Cryogenic facilities
Leaks from liquid nitrogen or argon can quickly create oxygen-poor atmospheres.
Battery and energy storage facilities
Various process gases can affect oxygen levels in case of leakage or ventilation problems.
Therefore, oxygen monitoring is important
When working in enclosed or poorly ventilated spaces, oxygen monitoring is often as important as monitoring toxic or flammable gases. Oxygen detectors alert when oxygen levels drop below safe levels and help protect personnel before oxygen deficiency leads to serious consequences.
Especially important choking gases to monitor
- Nitrogen (N₂)
- Carbon dioxide (CO₂)
- Argon (Ar)
- Helium (He)
- Cryogenic gases (liquid nitrogen and argon)
These gases are often found in industries, energy facilities, laboratories, food production and welding environments where oxygen monitoring is an important part of safety work.